Fault codes for the GeniaAir heat pump

Fault codesMeaningPossible cause
F.22Low water pressure in the systemThe water pressure in your system is below the normal range of 1 to 1.5 bar, loose, disconnected, or faulty wiring for the pressure sensor, water pressure sensor faulty, expansion vessel faulty
F.42Coding resistor faultCoding resistor damaged or not set, damage to coding resistor wiring harness
F.283De-icing was unsuccessfulElectric back-up heater is not sufficient or is not available at all, insufficient heat energy in the house installation, ice formation on the evaporator
F.514Compressor inlet temperature sensor faultFault in the electrical connection for the compressor inlet temperature sensor, compressor inlet temperature sensor defective
F.517Compressor outlet temperature sensor faultFault in the electrical connection for the compressor outlet temperature sensor, compressor outlet temperature sensor defective
F.519Building circuit return temperature sensor faultFault in the electrical connection for the building circuit return temperature sensor,
building circuit return temperature sensor defective
F.520Building circuit flow temperature sensor faultFault in the electrical connection for the building circuit flow temperature sensor, building circuit flow temperature sensor defective
F.526Evaporator inlet temperature sensor faultFault in the electrical connection for the evaporator inlet temperature sensor, evaporator inlet temperature sensor defective
F.546Refrigerant high pressure sensor faultFault in the electrical connection for the refrigerant high pressure sensor, refrigerant high pressure sensor defective
F.582Electric expansion valve faultFault in the electrical connection for the electric expansion valve,
electric expansion valve defective
F.585Condenser outlet temperature sensor faultFault in the electrical connection for the condenser outlet temperature sensor, condenser outlet temperature sensor defective
F.703Low refrigerant pressure sensor faultRefrigerant levels too low
Incondensable particles in the refrigerant circuit,
electronic expansion valve fault, fault in the electrical connection of the Low-pressure sensor, low-pressure sensor fault
F.718Fan unit blocked (fan 1 in the case of a twin fan heat pump)Damage or blockage to fan blade, faulty fan motor, fault in the electrical connection to the fan motor, HMU fault,
installer board fault
F.729Compressor outlet temperature too lowFault in the electrical connection of the compressor outlet temperature sensor, compressor outlet temperature sensor fault,
fault in the electrical connection of the high pressure sensor,
high pressure sensor fault, electronic expansion valve fault,
4 way valve fault, refrigerant volume too high
F.731Refrigerant high pressure switch openFault in the electrical connection of the high pressure switch,
high pressure switch fault, electronic expansion valve fault,
4 way valve fault, refrigerant flow too low, condenser blocked or restricted (see F.532),
building circuit flow rate too high or too low (see F.532)
F.732Compressor outlet temperature too highFault in the electrical connection of the compressor inlet or outlet temperature sensor, compressor inlet or outlet temperature sensor fault, electronic expansion valve fault, refrigerant volume too low,
building circuit flow rate too low, blocked or restricted filter or Y strainer, air in the building circuit
F.733Evaporation temperature too lowLack of servicing, dirt or debris blocking external air heat exchanger, compressor inlet temperature sensor, electronic expansion valve fault, refrigerant volume too low
F.734Condensation temperature too lowElectronic expansion valve fault, fault in the electrical connection of the compressor inlet temperature sensor, compressor inlet temperature sensor fault, low refrigerant volume, fault in the electrical connection of the high pressure sensor, high pressure sensor fault, building circuit pressure too low
F.735Evaporation temperature too highPoor air flow through the evaporator, poor heat transfer into the heating circuit (see F.733), electronic expansion valve fault, fault in the electrical connection of the evaporator temperature sensor, evaporator temperature sensor fault, high refrigerant volume
F.737Condensation temperature too highBuilding circuit flow rate too high or too low, lack of heat transfer into the building circuit, air in the building circuit, blocked or restricted filter or Y strainer, circulation pump, electronic expansion valve fault, refrigerant volume too high
F.739Low refrigerant volumeLow refrigerant volume, fault in the electrical connection of the compressor inlet or outlet temperature sensor, compressor inlet or outlet temperature sensor fault, fault in the electrical connection of the refrigerant low- or high-pressure sensor, refrigerant low- or high-pressure sensor fault
F.572Frequency convertor (invertor board) faultIncoming main voltage is not within permissible tolerances, electrical phases incorrect, reverse polarity, poor earthing, unstable power supply, fault in the wiring harness or connector to the invertor PCB, fault in the wiring harness or connector to the compressor, fault in the invertor PCB
F.753Frequency convertor (invertor board) not recognised/connection faultFault in the wiring harness or connector to the invertor PCB, fault in the wiring harness or connector to the compressor, fault in the invertor PCB
F.755Incorrect position of the 4-port valve4-ort valve stuck in the incorrect position,
4-port valve coil incorrectly fitted or faulty,
incorrectly positioned flow or return temperature sensor,
pipework incorrectly connected (flow and return pipework crossed),
fault in the electrical connection of the flow or return temperature sensor, fault in the electrical connection of the EEV temperature sensor, EEV temperature sensor fault
F.764Compressor phase errorSupply phase error/ fault or reversed (400v versions only),
Supply voltage too low or fluctuating, fault in the electrical connection to the invertor, invertor fault
F.785Fan unit 2 blockedDamage or blockage to fan blade, faulty fan motor, fault in the electrical connection to the fan motor, HMU fault,
Iinstaller board fault
F.788Building circuit pump faultFault in the electrical connection to the building circuit pump, fault in the wiring harness to the building circuit pump, faulty building circuit pump, air in the building circuit, blocked or restricted filter or Y strainer
F.817Frequency convertor (invertor PCB) fault – Compressor faultFault in the wiring harness or connector to the compressor, fault in the invertor PCB, compressor fault
F.818Frequency convertor (invertor PCB) fault – Mains voltage faultIncoming main voltage is not within permissible tolerances, electrical phases incorrect (400V versions only), reverse polarity, poor earthing, unstable power supply
F.819Invertor has overheatedBlockage or restriction in air flow through the invertor, maximum operating ambient temperature exceeded (46°C), faulty fan operation or damaged, invertor fault
F.820Building circuit pump connection faultFault in the wiring harness to the building circuit pump, faulty building circuit pump
F.823Compressor temperature switch has triggeredElectronic expansion valve (EEV) fault,
fault in the electrical connection to the EEV, contamination in the refrigerant circuit i.e. dirt or moisture
F.825Condenser inlet temperature sensor in the refrigerant circuitFault in the electrical connection for the compressor inlet temperature sensor, compressor inlet temperature sensor defective
F.1117Invertor phase failureIncoming main voltage is not within permissible tolerances, electrical phases incorrect (400V versions only), reverse polarity, poor earthing, unstable power supply
F.9997Communication between indoor and outdoor unit not possible due to incorrect communication protocolIncorrect appliance interface, fault in the wiring or connection between the heat pump and heat pump interface, incorrect connection of Ebus components to communication connection between indoor and outdoor units
F.9998Communication fault between the heat pump to all Ebus controllers/wiring centresIncoming main voltage is not within permissible tolerances to heat pump, fault in the wiring or connection between the heat pump interface and VR71, fault in the wiring or connection between the VR71 and any wireless receivers, reverse polarity in the Ebus connection at all terminals, insufficient cable diameter, min requirements 0.75mm twin core, induced current from mains cables, min 120mm separation distance, incorrect Ebus cable type, twisted multicore cables not permissible,
shielding cable not permissible unless suitably earthed, fault in the wiring or connection between the HMU and installer PCB, faulty HMU